Conventional type
Alarm Verification type (Alarm verification time
60seconds)
Various test functions : fire indication test, auxiliary
power supply test and alarm verification time test.
Durable LED indications
Back-up power supply (Ni-Cd battery, 24VDC)
Easy maintenace
Automatic self-checking system
DESCRIPTION
On receiving a fire signal from a fire detector or amanual alarm box, the FAP 230N-1L conventional fire alarm pahel gives a visual alarm,as wellas an audible alarm, to alert the alarm panel operator. lt also produces alarms to alert the occupants of the building premises.
Specification
Model No
FAP 230N-1L
TYPE
wall mounting type
POWER SUPPLY
220VAC 50/60Hz
AUX. POWER SUPPLY
Sealed Ni-Cd battery 0.1Ah
CIRCUIT VOLTAGE
24VDC
ALARM VERIFICATION TIME
Thermal deteclor 10sec.,Smoke detector 60sec.
POWER CONSUMPTION
Max.approx. : 9VA (ln normal condition)
Max.approx. : 10VA (ln alarming condition)
MAX. PERMISSIBLENUMBER OF APPARATUS TO BE CONNECTED
Smoke detectors : Up to 30
Local alarm bells :Upto 4 (For bell
of 24VDC, 10 mA)
lndicator LED : Up to 3 (For 24V, 21mA Light Emitting Dlode)