TA-CHA CO.,LTD.
FIRE ALARM SYSTEM FAP 230N -1L

FEATURES

  • Conventional type
    Alarm Verification type (Alarm verification time
    60seconds)
  • Various test functions : fire indication test, auxiliary
  • power supply test and alarm verification time test.
  • Durable LED indications
  • Back-up power supply (Ni-Cd battery, 24VDC)
  • Easy maintenace
  • Automatic self-checking system
DESCRIPTION  
On receiving a fire signal from a fire detector or amanual alarm box, the FAP 230N-1L conventional fire alarm pahel gives a visual alarm,as wellas an audible alarm, to alert the alarm panel operator. lt also produces alarms to alert the occupants of the building premises.

  Specification
Model No FAP 230N-1L
TYPE wall mounting type
POWER SUPPLY 220VAC 50/60Hz
AUX. POWER SUPPLY Sealed Ni-Cd battery 0.1Ah
CIRCUIT VOLTAGE 24VDC
ALARM VERIFICATION TIME Thermal deteclor 10sec.,Smoke detector 60sec.
POWER CONSUMPTION
  • Max.approx. : 9VA (ln normal condition)
  • Max.approx. : 10VA (ln alarming condition)
MAX. PERMISSIBLENUMBER OF APPARATUS TO BE CONNECTED
  • Smoke detectors : Up to 30
  • Local alarm bells :Upto 4 (For bell
  • of 24VDC, 10 mA)
    lndicator LED : Up to 3 (For 24V, 21mA Light Emitting Dlode)
AMBIENT TEMPERATURE O to 40'C
RESISTANCE OF ONE DETECTOR LINE less than 50 ???/ Loop
END-OF-LINE RESISTOR 10k??? 1/2 W
WEIGHT Aoprox. 1440g