FIRE ALARM SYSTEM

FEATURES
  • Save-cost and save-space
  • Available for 10 anc 20 fire alarm zones
  • Conventional type
  • Alarmverification type
  • Name plate and a digital display for alarmed zones
  • programmable ontput signal
  • Ni-Cd stand by battery builtin
  • Telephone handset built in for maontenance
  • programmablr function at site
  • Automatic self-checking
  • Various test facilites for maintenance
  • surge arrester built in for power lines

DESCRIPTION
The FAP 129 N seriels fire alarm panel was deceloped to provide a cost- and space -saving conventional fire alarm panel together withmore user -oriented functions. The size of the panel is approximately one-half te debth, one-half the area, one-fourth the volume, and one-fifth the weight of our last 20-zone fire alarm panel. The cabinet is made of ABS resin with non-flammability to UL-94V2.

<Alarminputs>
Conventional fire detectors and manual alarm boxes are connected to alarm input circuits to give visusl and audibe alarm at the paneland to actuate alarm bells. The FAP 129N series fire alarm panel has a line-up of 10 and 20 alarm input circuits ( zones ), Each alarm circuit has an alarm verification function.
<AUXiliary inputs>
Three auxiliary inout signais can be connected to auxiliary input circuits to be displayed it on the panel. They may be used for non-alarm input signals.
<Signal outputs>
2 representative alarm signals are available 10 voltage-free contacts are available for signal output. A group of output signal for an Annunciator panel. A group of signais for aFire p ump Starting Relay Box
<Digital display>
The 2-digit digital indicator displays not only alarming zones but also trouble which happened in the fire alarm panel and in the system.
<Alarm bell activation>
There are 2 modes to activate alarm bells. one is to actuate all alarm bells at the same time, called general alarm. The other is to actuate agroup of alarm bells depending on the location of terminals is available for the general alrm. The programmable 10 voltage-free contacts are used for the localized alarm.

<Automatic self-checking>
The following are automatically monitored at all time. .Detector circuits for con tinuity .Connection of the battery and fuse blown-out .Microcomputer chip and memory chips for abnormal running .Main fuses for blown-out .Connectors and signal transmission circuits for interruption of communication between PCBs .Main circuit voltage for ocer limit and under limit The alarm input circuits are automatically checked once a week for normal operation.
<programming>
The following are programmable for setting and canceling with a template on the panel.
Non used-alarm input circuits without putting dummy loads Alarm verification function to alarm-input circuits lnterlocking auxiliary input signals with an audible alarm at the panel lnterlocking alarm input signals with representative alarm signals An audible alarm at the panel during main power off lnterlocking alarm input signals with 10 voltage-free contact outputs
<Fire protection-related device control>
FAP129N series fire alarm panel has only fire alarm functions. FCS 129N series fire alarm panel is available not only for fire alarm functions but also control functions for fire protection-related devices such as smoke vents, fire extinguishing systemetc.