<Alarminputs>
Conventional fire detectors and manual alarm boxes are connected to alarm input circuits to give visusl and audibe alarm at the panel and to actuate alarm bells. The FAP128N series fire alarm panel has a line -up of 30,40 and 50-alarm input circuits (zones). Each alarm circuit has an alarm verification tunction.
<AUXiliary inputs>
Five auxiliary inout signais can be connected to auxiliary input circuits to be displayed it on the panel. They may be used for non-alarm input signals.
<Signal outputs>
2 representative alarm signals are available.
20 voltage-free contacts are available for signal output. A group of output signals for 2 Annunciator Panels (FLP116N). A group of signais for aFire p ump Starting Relay Box
<Digital display>
The 2-digit digital indicator displays not only alarming zones but also trouble which happened in the fire alarm panel and
in the system.
<Alarm bell activation>
There are 2 modes to activate alarm bells. one is to actuate all alarm bells at the same time, called general alarm. The other is to actuate agroup of alarm bells depending on the location of terminals is available for the general alrm. The programmable 20 voltage-free contacts are used for the localized alarm. |
|
<Automatic self-checking>
The following are automatically monitored at all time. Detector circuits for con tinuity
Connection of the battery and fuse blown-out Microcomputer chip and memory chips for abnormal running Main fuses for blown-out Connectors and signal transmission circuits for interruption of communication between PCBs Main circuit voltage for ocer limit and under limit The alarm input circuits are automatically checked once a week for normal operation.
<programming>
The following are programmable for setting and canceling with a template on the panel.
Non used-alarm input circuits without putting dummy loads Alarm verification function to alarm-input circuits lnterlocking auxiliary input signals with an audible alarm at the panel lnterlocking alarm input signals with representative alarm signals An audible alarm at the panel during main power off
lnterlocking alarm input signals with 20 voltage-free contact outputs
<Fire protection-related device control>
FAP129N series fire alarm panel has only fire alarm functions. FCS 128N series fire alarm panel is available not only for fire alarm functions but also control functions for fire protection-related devices such as smoke vents, fire extinguishing system etc. |